前言
本規(guī)程規(guī)定了姜堰市區(qū)行政區(qū)域內(nèi)新建、擴(kuò)建、改建工程的二次供水技術(shù)要求。
本規(guī)程主要內(nèi)容包括總則、術(shù)語、建設(shè)要求、水質(zhì)、水量與水壓、加壓方式與供水系統(tǒng)、水泵、水箱與壓力水容器、管道與閥門、控制、保護(hù)與安防、泵房、水質(zhì)保障、工程驗(yàn)收以及本規(guī)程用詞說明等十四項。
目次
一 總則·····················································1
二 術(shù)語·····················································2
三 建設(shè)要求·················································3
四 水質(zhì)、水量與水壓··········································4
五 加壓方式與供水系統(tǒng)·······································4
六 水泵·····················································5
七 水箱與壓力水容器·········································6
1 一般規(guī)定···············································6
2 水箱···················································7
3 壓力水容器············································8
八 管道與閥門··············································8
1 材質(zhì)··················································8
2 安裝··················································9
九 控制、保護(hù)與安防·········································10
1 控制··················································10
2 保護(hù)··················································11
3 安防··················································12
十 泵房····················································12
十一 水質(zhì)保障··············································13
1 一般規(guī)定············································13
2 消毒設(shè)備············································14
3 清洗消毒與水質(zhì)檢測··································14
十二 工程驗(yàn)收··············································15
1 一般規(guī)定············································15
2 竣工資料驗(yàn)收········································15
3 現(xiàn)場驗(yàn)收············································15
十三 本規(guī)程用詞說明········································17
十四 其它··················································17
一、總則
1、 為保障社會公眾利益,確保二次供水安全,提高姜堰市二次供水設(shè)施的建設(shè)水平,特制訂《姜堰市二次供水工程技術(shù)規(guī)程》。
2 、本規(guī)程適用于本市行政區(qū)域內(nèi)新建、擴(kuò)建、改建工程中二次供水的設(shè)計、施工、驗(yàn)收與監(jiān)督。
3 、二次供水工程的設(shè)計、施工與驗(yàn)收除應(yīng)執(zhí)行本規(guī)程外,尚應(yīng)符合國家、行業(yè)、地方現(xiàn)行有關(guān)標(biāo)準(zhǔn)的規(guī)定。
4、 本規(guī)程制定的主要依據(jù):
GB 150-1998《鋼制壓力容器》
GB/T 3797-2005《電氣控制設(shè)備》
GB 5749-2006 《生活飲用水衛(wèi)生標(biāo)準(zhǔn)》
GB/T 5750-2006《生活飲用水標(biāo)準(zhǔn)檢驗(yàn)方法》
GB 17051-1997 《二次供水設(shè)施衛(wèi)生規(guī)范》
GB/T 17219-1998《生活飲用水輸配水設(shè)備及防護(hù)材料的安全性評價標(biāo)準(zhǔn)》
GB 50015-2003 《建筑給水排水設(shè)計規(guī)范》
GB/T 50265-97 《泵站設(shè)計規(guī)范》
GB 50055-1993 《通用用電設(shè)備配電設(shè)計規(guī)范》
GB 50242-2002 《建筑給排水及采暖工程質(zhì)量驗(yàn)收規(guī)范》
GB 50245-1996 《電氣裝置安裝工程低壓電器施工及驗(yàn)收規(guī)范》
GB 7450-1987 《電子設(shè)備雷擊保護(hù)導(dǎo)則》
GB 50300-2001 《建筑工程施工質(zhì)量驗(yàn)收統(tǒng)一標(biāo)準(zhǔn)》
GB 50303-2002 《建筑電氣工程施工質(zhì)量驗(yàn)收規(guī)范》
JG/T 3009-1993 《微機(jī)控制變頻調(diào)速給水設(shè)備》
JB/T 8097-1999 《泵的振動測量與評價方法》
JB/T 8098-1999 《泵的噪聲測量與評價方法》
DB 29-22-2007 《江蘇省住宅設(shè)計標(biāo)準(zhǔn)》
二、術(shù)語
1、 二次供水
是指對超過城市供水管網(wǎng)正常服務(wù)壓力要求的建筑物,在入戶前再次通過儲存、加壓等設(shè)施向用戶提供用水的方式。
2、 二次供水設(shè)施
為二次供水設(shè)置的水箱(池)、水泵、閥門、氣壓罐、消毒設(shè)備、電控裝置、供水管道、泵房等設(shè)施。
3、水箱通氣管
為使水箱與大氣相通而設(shè)置的管道。
4、溢流管
為防止水箱(池)內(nèi)的水超出允許的最高水位而設(shè)置的放水管。
5、泄水管
為排空水箱(池)內(nèi)的水而設(shè)置的管道。
6、水箱人孔
為對水箱進(jìn)行檢修或清洗消毒而設(shè)置的人員出入通道。
7、涉及飲用水衛(wèi)生安全的產(chǎn)品(簡稱“涉水產(chǎn)品”)
在飲用水生產(chǎn)和供水過程中與飲用水接觸的材料、顏料及有機(jī)合成管材、管件、防護(hù)涂料、水處理劑、除垢劑、水質(zhì)處理器及其他新材料和化學(xué)物質(zhì)。
8、消毒
用化學(xué)、物理、生物的方法殺滅或消除環(huán)境中致病微生物的一種措施。
三、建設(shè)要求
1、二次供水應(yīng)遵循安全、衛(wèi)生、節(jié)能、環(huán)保的原則。
2、當(dāng)新建工程用戶用水最低工作壓力要求大于市政給水管網(wǎng)實(shí)際供水壓力時,應(yīng)設(shè)置二次供水設(shè)施。
3、二次供水設(shè)施必須獨(dú)立設(shè)置,應(yīng)和市政給水管網(wǎng)或居住小區(qū)的供水能力相匹配,并應(yīng)有建筑維護(hù)結(jié)構(gòu)。
4、二次供水設(shè)施必須與主體工程同時設(shè)計、同時施工、同時投入使用。
5、二次供水在施工圖設(shè)計前,設(shè)計單位應(yīng)根據(jù)確定的建筑方案、總平面圖和工程現(xiàn)場周邊市政供水管網(wǎng)資料,會同供水企業(yè)共同確定二次供水設(shè)計方案。二次供水設(shè)計方案經(jīng)供水行政主管部門批準(zhǔn)認(rèn)可,方能進(jìn)行施工圖設(shè)計。
6、分期開發(fā)建設(shè)的小區(qū)應(yīng)按整體規(guī)劃建設(shè)生活用水增壓泵房,土建工程一次建設(shè),設(shè)備安裝分期實(shí)施。
7、二次供水設(shè)施必須采取有效的防污染措施。
8、二次供水設(shè)施應(yīng)有防凍、防曝曬、防雷擊等有效防護(hù)措施。
9、二次供水設(shè)施應(yīng)有銘牌,標(biāo)明生產(chǎn)單位、注冊商標(biāo)、生產(chǎn)日期、出廠編號、執(zhí)行標(biāo)準(zhǔn)、技術(shù)參數(shù)以及衛(wèi)生許可批件或其他有效的衛(wèi)生安全證明文件等主要內(nèi)容。
四、水質(zhì)、水量與水壓
1、二次供水水質(zhì)應(yīng)符合GB 5749《生活飲用水衛(wèi)生標(biāo)準(zhǔn)》的規(guī)定。
2、二次供水水量應(yīng)根據(jù)建筑物使用性質(zhì)、衛(wèi)生器具和用水設(shè)備的完善程度確定,水量應(yīng)符合GB 50015《建筑給水排水設(shè)計規(guī)范》與DB 29-22《江蘇省住宅設(shè)計標(biāo)準(zhǔn)》的有關(guān)規(guī)定。
3、二次供水系統(tǒng)供水壓力應(yīng)根據(jù)最不利點(diǎn)衛(wèi)生器具和用水設(shè)備的最低工作壓力確定。
五、加壓方式與供水系統(tǒng)
1、二次供水形式的選擇,一般可用水箱(池)加變頻泵、水箱(池)加泵加屋頂水箱的增壓系統(tǒng)以及疊壓供水系統(tǒng)等;高層二次供水應(yīng)有合理的豎向分區(qū),不宜采用高能耗一次加壓后再采用減壓閥分區(qū)降壓供水的方式。
2、在市政給水管網(wǎng)條件允許的情況下,可以選擇管網(wǎng)疊壓供水形式。
存在下列條件之一的不應(yīng)采用管網(wǎng)疊壓供水設(shè)施:
⑴、市政給水管網(wǎng)可利用的水頭過低的區(qū)域;
⑵、市政給水管網(wǎng)供水的水量、水壓波動過大的區(qū)域;
⑶、使用疊壓供水設(shè)備對周邊(現(xiàn)有或規(guī)劃)用戶用水會造成較大影響的區(qū)域;
⑷、供水保證率要求高,需要連續(xù)供水不允許停水的用戶;
3、疊壓供水配置低位水箱時,其貯水有效容積應(yīng)按給水管網(wǎng)不允許低水壓抽水時段的用水量確定,并應(yīng)采取技術(shù)措施保證貯水在水箱中停留時間不得超過12h;
4、使用變頻泵加壓供水時,宜采用氣壓供水等裝置,減少夜間等時段用水量很少增壓泵持續(xù)運(yùn)行保壓的狀況。
5、二次供水增壓站的位置、規(guī)模、水壓應(yīng)結(jié)合居住小區(qū)規(guī)模、分期建設(shè)情況、建筑高度、建筑物的分布以及系統(tǒng)維護(hù)和安全運(yùn)行等因素,經(jīng)技術(shù)經(jīng)濟(jì)比較后予以確定。應(yīng)結(jié)合附近小區(qū)建設(shè)優(yōu)先考慮集中建設(shè)加壓泵站。
6、二次供水增壓站的引入管宜從居住小區(qū)給水管網(wǎng)或市政給水管網(wǎng)單獨(dú)引入。
7、二次供水豎向分區(qū)應(yīng)根據(jù)二次供水形式,建筑物用途、建筑高度、使用要求、能耗、材料設(shè)備性能、維護(hù)管理等因素,依照相關(guān)規(guī)范綜合確定。
8、二次供水范圍內(nèi),使用性質(zhì)不同或水費(fèi)單價不同的用水,應(yīng)分系統(tǒng)分表計量。
六、水泵
1、居住建筑二次供水設(shè)施選用的水泵噪聲應(yīng)符合JB/T 8098《泵的噪聲測量與評價方法》標(biāo)準(zhǔn)中的B級;水泵振動應(yīng)符合JB/T 8097《泵的振動測量與評價方法》標(biāo)準(zhǔn)中的B級。
2、公共建筑二次供水設(shè)施選用的水泵噪聲應(yīng)符合JB/T 8098《泵的噪聲測量與評價方法》標(biāo)準(zhǔn)中的C級;水泵振動應(yīng)符合JB/T 8097《泵的振動測量與評價方法》標(biāo)準(zhǔn)中的C級。
3、對噪聲和振動有更高要求的建筑,二次供水設(shè)施水泵的選擇應(yīng)符合相關(guān)要求。
4、水泵宜采用自灌式安裝。
5、水泵吸水管設(shè)計流速宜為0.8~1.2m/s,出水總管設(shè)計流速宜≤1.5m/s。
6、二次供水設(shè)備應(yīng)設(shè)置備用水泵。
7、水泵采用變頻控制時,水泵在額定轉(zhuǎn)速時的工況點(diǎn)應(yīng)位于水泵流量揚(yáng)程曲線的高效區(qū)右端。
8、水泵機(jī)組變頻控制時,宜采用多臺工作泵,水泵應(yīng)能自動交替工作、互為備用運(yùn)行操作應(yīng)能自動切換及手動切換。
9、水泵機(jī)組采用變頻調(diào)速控制時,每臺水泵宜設(shè)置單獨(dú)的變頻器。
10、系統(tǒng)采用氣壓給水設(shè)備供水時,其有效容積應(yīng)與水泵最大允許啟停次數(shù)相匹配。
七、水箱與壓力水容器
1、一般規(guī)定
⑴、水箱和壓力水容器應(yīng)符合GB 50015-2003 《建筑給水排水設(shè)計規(guī)范》、GB 17051-1997 《二次供水設(shè)施衛(wèi)生規(guī)范》、GB/T 17219《生活飲用水輸配水設(shè)備及防護(hù)材料的安全性評價標(biāo)準(zhǔn)》的有關(guān)規(guī)定。
⑵、水箱和壓力水容器宜優(yōu)先選用符合國家生活飲用水衛(wèi)生標(biāo)準(zhǔn)的不銹鋼材料,焊接材料應(yīng)與水箱同材質(zhì),不銹鋼焊縫應(yīng)進(jìn)行酸洗鈍化等抗氧化處理;可使用SMC鋼化玻璃、聚乙烯、鋼板搪瓷襯里等材料,嚴(yán)禁使用混凝土、手糊玻璃鋼、普通鋼板材料。
⑶、水箱及壓力水容器的環(huán)境溫度低于4℃時,應(yīng)采取保溫措施。
2、水箱
⑴、住宅低位水箱貯水容積應(yīng)按進(jìn)水量與用水量變化曲線經(jīng)計算確定,當(dāng)資料不足時,居住小區(qū)可按最高日用水量的10%~15%確定,單幢住宅樓宜按最高日用水量的50%確定;高位水箱調(diào)節(jié)容積宜按水箱服務(wù)區(qū)域內(nèi)的最大小時用水量的50%確定。
⑵、水箱容積大于30m3時,必須分為容積基本相等的兩格,并能獨(dú)立工作。
⑶、建筑物內(nèi)水池(箱)側(cè)壁與墻面間距不宜小于0.7m,安裝有管道的側(cè)面,凈距不宜小于1.0m;水池(箱)與室內(nèi)建筑凸出部分間距不宜小于0.5m;水池(箱)頂部與樓板間距不宜小于0.8m;水池(箱)底部應(yīng)架空,距地面不宜小于0.5m,并應(yīng)具有排水條件。
⑷、水箱高度不宜超過3m。當(dāng)水箱高度≥1.5m時,水箱內(nèi)外應(yīng)設(shè)爬梯。水箱內(nèi)爬梯、支撐件及配件等,必須使用符合國家飲用水衛(wèi)生標(biāo)準(zhǔn)的不銹鋼材料。
⑸、水箱必須設(shè)置人孔。圓型人孔直徑應(yīng)≥0.6m,方型人孔每邊長應(yīng)≥0.6m,水箱人孔必須設(shè)有帶鎖的密封蓋,密封蓋上應(yīng)有凹槽并加設(shè)密封圈,人孔保護(hù)高度應(yīng)≥0.1m。
⑹、水箱宜優(yōu)先選擇頂部進(jìn)水;在水箱側(cè)面設(shè)置進(jìn)水管時,進(jìn)水管與出水管應(yīng)采取相對方向設(shè)置,必要時應(yīng)設(shè)導(dǎo)流裝置。
⑺、水箱進(jìn)水管管底應(yīng)高于溢流管管頂,距離應(yīng)≥0.1m;水箱出水管管底距水箱底部應(yīng)≥0.1m。
⑻、水箱進(jìn)水管與出水管上必須安裝閥門,且進(jìn)水管應(yīng)安裝具有機(jī)械和電氣雙重控制功能的水位控制閥。
⑼、水箱溢流管管徑應(yīng)大于進(jìn)水管管徑;宜采用水平喇叭口集水;溢流管管口應(yīng)設(shè)置18目的耐腐蝕材料濾網(wǎng)。
⑽、水箱泄水管必須設(shè)在水箱底部,管徑應(yīng)≥DN50,,水箱底部應(yīng)有不小于0.01的坡度,坡向泄水管。
⑾、水箱溢流管、泄水管嚴(yán)禁與排水系統(tǒng)直接相連,應(yīng)有不小于0.1m的空氣隔斷。
⑿、水箱必須設(shè)置通氣管,管徑應(yīng)≥DN25,通氣管口應(yīng)安裝孔徑為40μm的微孔過濾器。
3、壓力水容器
⑴、壓力水容器除應(yīng)滿足一般標(biāo)準(zhǔn)的規(guī)定外,還應(yīng)滿足GB 150《鋼制壓力容器》的規(guī)定。
⑵、壓力水容器的設(shè)計壓力應(yīng)符合國家有關(guān)技術(shù)標(biāo)準(zhǔn)的規(guī)定。
八、管道與閥門
1、材質(zhì)
⑴、埋地給水管道應(yīng)根據(jù)承受壓力等級、地面荷載力的不同選出耐腐蝕、壽命長的管材、管件。應(yīng)優(yōu)先選用有內(nèi)襯的球墨鑄鐵管和有可靠內(nèi)外防腐的金屬管道等。
⑵、建筑物內(nèi)給水管道應(yīng)優(yōu)先選用耐壓、耐腐蝕、安裝方便的銅管、不銹鋼管、襯塑鋼管等。
⑶、應(yīng)選用趨于直線、關(guān)閉靈活、耐腐蝕、壽命長的閥門,宜優(yōu)先選用銅、不銹鋼或閥體為球墨鑄鐵,閥桿、閥芯為不銹鋼或銅材質(zhì)的閥門。閥板宜為軟橡膠密封。
⑷、浮球閥的浮球、連接桿必須為不銹鋼或銅材質(zhì)。
⑸、除污器濾網(wǎng)應(yīng)為不銹鋼或銅材質(zhì),濾網(wǎng)宜為20~40目。
2、安裝
⑴、嚴(yán)禁二次供水管道與非飲用水管道直接連通連接。
⑵、建筑內(nèi)貿(mào)易結(jié)算水表前的供水管道必須設(shè)置在建筑的公共部位,可設(shè)置在管道井內(nèi),但應(yīng)有水表間或水表箱,水表間應(yīng)設(shè)進(jìn)出門。水表箱應(yīng)設(shè)置在戶外便于檢修、抄讀,不受曝曬、凍結(jié)、污染和機(jī)械等外力損傷的地方。
⑶、二次供水管道應(yīng)作藍(lán)色標(biāo)識,并標(biāo)明二次供水。
⑷、二次供水的進(jìn)、出水總管上應(yīng)設(shè)置手動、電動雙重閥門。
⑸、二次供水引入樓內(nèi)的立管應(yīng)在建筑物首層設(shè)置閥門。
⑹、倒流防止器的設(shè)置必須符合GB 50015-2003 《建筑給水排水設(shè)計規(guī)范》的有關(guān)規(guī)定,并應(yīng)選用空氣隔斷型,流速在2m/s時,水頭損失≤0.03MPa、體積尺寸相對較小、具有自動排水功能、維修簡便、耐用的倒流防止器。
⑺、建筑物內(nèi)二次供水立管最高點(diǎn)或室外給水管網(wǎng)有明顯起伏的管段峰點(diǎn)應(yīng)設(shè)置自動排氣閥。
九、控制、保護(hù)與安防
1、控制
⑴、設(shè)備控制設(shè)計應(yīng)符合GB 50055《通用用電設(shè)備配電設(shè)計規(guī)范》的規(guī)定。
⑵、二次增壓供水系統(tǒng)應(yīng)具有自動化控制設(shè)計,自控系統(tǒng)具有現(xiàn)場控制和遠(yuǎn)程控制兩種模式,其運(yùn)行模式可通過現(xiàn)場控制柜上人機(jī)界面的選擇開關(guān)進(jìn)行切換。其中,現(xiàn)場控制又具有現(xiàn)場人工控制和現(xiàn)場自動控制兩種模式,遠(yuǎn)程控制也同樣具有遠(yuǎn)程手動控制和遠(yuǎn)程程序控制兩種模式。其優(yōu)先級從高到底順序?yàn)椋含F(xiàn)場人工控制 、遠(yuǎn)程控制、現(xiàn)場全自動控制、遠(yuǎn)程程控控制。
⑶、變頻供水設(shè)備應(yīng)采用恒壓變量供水或變壓變量供水方式。
⑷、設(shè)備應(yīng)能自動進(jìn)行小流量運(yùn)行控制。
⑸、設(shè)備應(yīng)顯示運(yùn)行狀態(tài)信號:電源、水源、水泵、消毒設(shè)備等;應(yīng)顯示運(yùn)行參數(shù):電壓、電流、液位、頻率(變頻控制設(shè)備)、進(jìn)水壓力(設(shè)定值及實(shí)際值)、供水壓力(設(shè)定值及實(shí)際值)等;應(yīng)顯示故障信號:過壓、欠壓、欠流、缺相、消毒設(shè)備、倒流防止器等。
⑹、變頻調(diào)控控制時,設(shè)備供水壓力控制與顯示精度應(yīng)≤0.01MPa。
⑺、設(shè)備檢測儀表的量程應(yīng)為工作點(diǎn)的1.5~2倍,儀表安裝應(yīng)符合相應(yīng)技術(shù)標(biāo)準(zhǔn)要求。
⑻、變頻供水電控柜(箱)應(yīng)符合JG/T3009《微機(jī)控制變頻調(diào)速給水設(shè)備》的規(guī)定。
⑼、住宅二次供水自控系統(tǒng)須具有設(shè)備運(yùn)行狀態(tài)數(shù)據(jù)采集、傳輸、遠(yuǎn)程監(jiān)測監(jiān)控及功能參數(shù)越界報警功能,應(yīng)有人機(jī)對話功能,界面應(yīng)漢化,圖標(biāo)應(yīng)明顯、顯示清晰、便于操作。
⑽、新建住宅二次供水設(shè)施應(yīng)能提供標(biāo)準(zhǔn)串行通訊接口和網(wǎng)絡(luò)接口,滿足自動運(yùn)行以及遠(yuǎn)傳遠(yuǎn)控各項要求。
⑾、計量水表應(yīng)采用智能水表。采用智能遠(yuǎn)傳水表時,遠(yuǎn)傳線路一般設(shè)置在智能化管廊內(nèi),同時應(yīng)有單獨(dú)開戶電源提供給智能遠(yuǎn)傳水表集抄系統(tǒng)。
2、保護(hù)
⑴、應(yīng)有滿足設(shè)備安全運(yùn)行的電源。
⑵、設(shè)備的電控柜(箱)的抗干擾能力應(yīng)符合相應(yīng)技術(shù)標(biāo)準(zhǔn)的要求。
⑶、設(shè)備進(jìn)水?dāng)嗨ɑ蛉彼?yīng)能自動報警及停機(jī)保護(hù),當(dāng)進(jìn)水恢復(fù)正常時,設(shè)備應(yīng)能自動啟動,正常運(yùn)行。
⑷、設(shè)備應(yīng)具有對過壓、欠壓、欠流、缺相、消毒設(shè)備等故障進(jìn)行報警及自動保護(hù)功能。對可恢復(fù)的故障,應(yīng)能自動或手動消除,恢復(fù)正常運(yùn)行。
⑸、設(shè)備應(yīng)有可靠的安全接地保護(hù),并符合相應(yīng)技術(shù)標(biāo)準(zhǔn)的要求。
⑹、設(shè)備中不等電位的裸導(dǎo)體之間,以及帶電的裸導(dǎo)體與金屬零、部件或接地零、部件之間的電氣間隙和爬電距離應(yīng)符合GB/T 3797《電氣控制設(shè)備》的有關(guān)規(guī)定。
⑺、設(shè)備的介電強(qiáng)度應(yīng)符合GB/T 3797《電氣控制設(shè)備》的有關(guān)規(guī)定。
⑻、倒流防止器持續(xù)排水時間超過1分鐘時,設(shè)備應(yīng)能報警。
⑼、水箱應(yīng)有可靠的液位控制裝置,當(dāng)水箱超高液位或超低液位及溢流時應(yīng)自動停機(jī)報警。
⑽、電氣設(shè)備安全性能必須符合國家規(guī)定,具有優(yōu)良的抗干擾能力。控制柜應(yīng)具有可靠的防雷擊措施,并應(yīng)符合GB 7450-1987《電子設(shè)備雷擊保護(hù)導(dǎo)則》的規(guī)定。
3、安防
泵房采用智能監(jiān)控系統(tǒng),應(yīng)設(shè)置異常情況的報警裝置并與視頻監(jiān)視系統(tǒng)聯(lián)動,實(shí)現(xiàn)報警信號、視頻信號與自動控制系統(tǒng)同步遠(yuǎn)傳。
十、泵房
1、新建居住小區(qū)建筑的泵房應(yīng)在建筑整體規(guī)劃時同時規(guī)劃。泵房應(yīng)采用地面泵房方案,在居住建筑之外獨(dú)立設(shè)置,其環(huán)境噪聲與振動應(yīng)符合國家有關(guān)技術(shù)標(biāo)準(zhǔn)的規(guī)定。
2、住宅泵房應(yīng)有可貿(mào)易結(jié)算的獨(dú)立可靠電源,應(yīng)采用雙電源或雙回路供電方式,并應(yīng)從公共通道直接進(jìn)入。
3、居住建筑的泵房應(yīng)安裝防盜門,其尺寸應(yīng)滿足搬運(yùn)最大設(shè)備的需要,窗戶及通風(fēng)孔應(yīng)設(shè)防護(hù)格柵式網(wǎng)罩。
4、增壓泵房應(yīng)合理布置,除應(yīng)考慮水箱或穩(wěn)流罐、管線、控制柜等設(shè)施外,還應(yīng)考慮有足夠的巡檢和維修間距,泵房凈高一般不低于3米,根據(jù)增壓規(guī)模,泵房面積最低不小于30m2。
5、泵房內(nèi)電器控制系統(tǒng)宜與水泵機(jī)組、水箱等輸配水設(shè)備隔離設(shè)置,并有防水、防潮措施。電器自動控制系統(tǒng)應(yīng)高出泵房地面50cm。
6、泵房的內(nèi)墻、地面應(yīng)選用符合環(huán)保要求、易清潔的材料鋪砌或涂覆,泵房內(nèi)應(yīng)整潔,嚴(yán)禁存放易燃、易爆、易腐蝕及可能造成環(huán)境污染的物品。
7、泵房應(yīng)設(shè)置排水系統(tǒng),泵房內(nèi)地面應(yīng)有不小于0.01的坡度向排水設(shè)施。
8、泵房應(yīng)通風(fēng)良好,已建泵房如設(shè)置在地下室時,應(yīng)設(shè)置通風(fēng)裝置,房間內(nèi)每小時換氣次數(shù)為2~3次。
9、泵房距污染源、污染物的距離應(yīng)符合國家有關(guān)規(guī)定。
十一、水質(zhì)保障
1、一般規(guī)定
⑴、二次供水設(shè)施不應(yīng)對水質(zhì)產(chǎn)生污染。
⑵、管網(wǎng)疊壓供水設(shè)施引入管上應(yīng)設(shè)置低阻力倒流防止器。
⑶、二次供水設(shè)施中輸配水設(shè)備、配件、水質(zhì)處理劑(器)、與水接觸的防護(hù)涂料和粘合劑等涉水產(chǎn)品均應(yīng)符合國家標(biāo)準(zhǔn)《生活飲用水輸配水設(shè)備及防護(hù)材料的安全性評價標(biāo)準(zhǔn)》GB/T 17219-1998的規(guī)定。
⑷、二次供水設(shè)施設(shè)置水箱(池)時,應(yīng)獨(dú)立設(shè)置,不宜置于室外,不得與消防用水或其它非生活用水共貯。
⑸、二次供水水箱(池)必須定期清洗消毒,每半年不得少于一次,并保證消毒效果。
⑹、二次供水應(yīng)根據(jù)水箱(池)的材質(zhì)選擇相應(yīng)的消毒劑,不得采用單純依靠投放消毒劑的清洗消毒方式。
⑺、二次供水管道應(yīng)避開有毒有害物質(zhì)污染區(qū)域。
2、消毒設(shè)備
⑴、消毒設(shè)備應(yīng)安全、衛(wèi)生、環(huán)保、節(jié)能、便于安裝檢修、有效、耐用和運(yùn)行經(jīng)濟(jì)。
⑵、應(yīng)選用紫外線消毒器、臭氧發(fā)生器和水箱自潔消毒器等安全可靠的消毒設(shè)備,其設(shè)計和安裝使用應(yīng)符合相關(guān)技術(shù)標(biāo)準(zhǔn)的要求。
3、清洗消毒與水質(zhì)檢測
⑴、二次供水設(shè)施安裝調(diào)試后應(yīng)對供水設(shè)備、管道進(jìn)行沖洗和消毒,并進(jìn)行水質(zhì)檢測。
⑵、二次供水設(shè)備清洗消毒后的水質(zhì)檢測結(jié)果應(yīng)符合國家標(biāo)準(zhǔn)GB 5749《生活飲用水衛(wèi)生標(biāo)準(zhǔn)》的規(guī)定。
⑶、二次供水的水質(zhì)檢測應(yīng)包括以下指標(biāo):色度、渾濁度、臭和味、肉眼可見物、pH值、耐熱大腸菌群、菌落總數(shù)、余氯、氨氮、亞硝酸鹽氮、鐵、總大腸菌群、耗氧量。特殊情況下可加檢其他指標(biāo)。
⑷、二次供水設(shè)施清洗消毒與水質(zhì)檢測頻率應(yīng)遵循國家、行業(yè)和地方的有關(guān)標(biāo)準(zhǔn)要求。
⑸、二次供水水樣采集、保存、運(yùn)輸和檢驗(yàn)按照GB/T 5750《生活飲用水標(biāo)準(zhǔn)檢驗(yàn)方法》執(zhí)行。
十二、工程驗(yàn)收
1、一般規(guī)定
⑴、工程竣工綜合驗(yàn)收前,應(yīng)及時對二次供水工程進(jìn)行專項驗(yàn)收。
⑵、驗(yàn)收程序:
①、工程竣工資料驗(yàn)收;
②、現(xiàn)場驗(yàn)收
③、出具驗(yàn)收報告。
2、竣工資料驗(yàn)收
⑴、二次供水工程資料:
①、二次供水工程的設(shè)計、變更設(shè)計圖紙;
②、隱蔽工程驗(yàn)收資料;
③、二次供水工程竣工圖紙;
④、二次供水設(shè)備的資質(zhì)材料。
⑵、衛(wèi)生、環(huán)保資料:
①、衛(wèi)生許可證或衛(wèi)生許可批件;
②、水質(zhì)檢測報告;
③、清洗消毒合格證;
④、泵房環(huán)境噪聲及振動檢測報告。
3、現(xiàn)場驗(yàn)收
⑴、泵房設(shè)置及其環(huán)境驗(yàn)收內(nèi)容:
①、泵房的設(shè)置;
②、泵房內(nèi)二次供水設(shè)施的設(shè)置;
③、泵房排水系統(tǒng);
④、泵房通風(fēng)系統(tǒng);
⑤、泵房保溫措施;
⑥、泵房電源;
⑦、泵房防雷擊設(shè)施;
⑧、泵房及周邊環(huán)境;
⑨、泵房及比鄰住宅環(huán)境噪聲與振動。
⑵、二次供水設(shè)施驗(yàn)收內(nèi)容
①、設(shè)備材質(zhì);
②、設(shè)備供水參數(shù);
③、設(shè)備顯示儀表;
④、設(shè)備控制與數(shù)據(jù)傳輸系統(tǒng);
⑤、設(shè)備接地等保護(hù)功能;
⑥、水泵機(jī)組設(shè)置;
⑦、水箱及壓力水容器;
⑧、閥門與管道設(shè)置。
⑶、工程施工質(zhì)量應(yīng)符合GB 50242《建筑給排水及采暖工程質(zhì)量驗(yàn)收規(guī)范》及GB 50300《建筑工程施工質(zhì)量驗(yàn)收統(tǒng)一標(biāo)準(zhǔn)》的規(guī)定。
⑷、機(jī)電設(shè)備安裝質(zhì)量應(yīng)符合GB 50303《建筑電氣工程施工質(zhì)量驗(yàn)收規(guī)范》及GB 50254《電氣裝置安裝工程低壓電器施工及驗(yàn)收規(guī)范》的規(guī)定。
⑸、二次供水水質(zhì)各項指標(biāo)應(yīng)符合GB 5749《生活飲用水衛(wèi)生標(biāo)準(zhǔn)》的規(guī)定。
十三、本規(guī)程用詞說明
執(zhí)行本規(guī)程條文時,對要求嚴(yán)格程度的用詞作如下規(guī)定,以便執(zhí)行時區(qū)別對待。
1、表示很嚴(yán)格,非這樣做不可的用詞:
正面詞采用“必須”;
反面詞采用“嚴(yán)禁”。
2、表示嚴(yán)格,在正常情況下均應(yīng)這樣的用詞:
正面詞采用“應(yīng)”;
反面詞采用“不應(yīng)”。
3、對表示容許稍有選擇,在條件許可時,首先應(yīng)該這樣做的用詞:
正面詞采用“宜”或“可”;
反面詞采用“不宜”。
十四、其它
本規(guī)程由姜堰市住房和城鄉(xiāng)建設(shè)局負(fù)責(zé)解釋。